ISO 9001 · 14001 · 45001 Certified Cable Manufacturer info@incabcables.com 9310301355

Extension / Compensating (Thermocouple) Cable

Colour-coded compensating cable that accurately extends thermocouple signals to instrumentation.

Type J/K/T/R-SColour-codedANSI MC96.1
VoltageSignal level (not power-rated)
Temperature-20°C to 105°C (PVC); up to 400°C (fibreglass)
StandardANSI MC96.1
Request a Quote
Technical Specifications
Construction
ConductorThermocouple alloy pair (Type J / K / T / R-S per requirement)
Conductor size range0.5 – 2.5 sq.mm
Number of cores/pairs1 pair / 2 pair, shielded or unshielded
InsulationPVC / Glass-fibre / Fibreglass (per temperature grade)
Inner sheathExtruded PVC bedding (multi-pair)
Shielding/screenOverall shield + drain wire (optional)
ArmourGI wire braid (optional, for fibreglass variant)
Outer sheathPVC / FRLS or fibreglass braid (high-temp variant)
Ratings & Standards
Voltage gradeSignal level (not power-rated)
Temperature rating-20°C to 105°C (PVC); up to 400°C (fibreglass)
Applicable standardsANSI MC96.1, BS EN 60584-3 (colour coding)
Special propertiesColour-coded per thermocouple type, matched thermal EMF
Thermocouple & Extension Cable Colour Codes

ANSI MC96.1 and IEC 584-3 colour coding, alloy combinations and EMF output by thermocouple type.

Thermocouple and extension cable colour coding chart, ANSI MC96.1 and IEC 584-3
ANSI
Code
ANSI MC 96.1 Colour CodingAlloy CombinationMaximum T/C Grade Temp. RangeEMF (mV) Over Max. Temp. RangeIEC 584-3
Colour Coding
IEC
Code
ThermocoupleExtension+ Lead− Lead
K+−+−Nickel-ChromiumNi-CrNickel-AluminumNi-Al-270 to 1372°C-454 to 2501°F-6.458 to 54.886+−K
J+−+−IronFe (magnetic)Constantan Copper-NickelCu-Ni-210 to 1200°C-346 to 2193°F-8.095 to 69.553+−J
T+−+−CopperCuConstantan Copper-NickelCu-Ni-270 to 400°C-454 to 752°F-6.258 to 20.872+−T
E+−+−Nickel-ChromiumNi-CrConstantan Copper-NickelCu-Ni-270 to 1000°C-454 to 1832°F-9.835 to 76.373+−E
N+−+−NicrosilNi-Cr-SiNisilNi-Si-Mg-270 to 1300°C-450 to 2372°F-4.345 to 47.513+−N
SNone
Established
+−Platinum-10% RhodiumPt-10%RhPlatinumPt-50 to 1768°C-58 to 3214°F-0.236 to 18.693+−S
RNone
Established
+−Platinum-13% RhodiumPt-13%RhPlatinumPt-50 to 1768°C-58 to 3214°F-0.226 to 21.101+−R
BNone
Established
+−Platinum-30% RhodiumPt-30%RhPlatinum-6% RhodiumPt-6%Rh0 to 1820°C32 to 3308°F0 to 13.820+−B

Colour illustrations show the jacket with the positive (+) and negative (−) conductor insulation. Supplied as per the ANSI MC96.1 or IEC 584-3 standard of your choice.

Applications
Thermocouple signal extension
Furnace & kiln temperature monitoring
Process temperature instrumentation
Boiler & heat-treatment plants
Get In Touch

Have a specification? Get a quote in 24 hours.

Send us your cable requirement and our team will revert with pricing and lead time.

24-Hour Response ISO 9001 Certified 9310301355