Extension / Compensating (Thermocouple) Cable
Colour-coded compensating cable that accurately extends thermocouple signals to instrumentation.
Type J/K/T/R-SColour-codedANSI MC96.1
VoltageSignal level (not power-rated)
Temperature-20°C to 105°C (PVC); up to 400°C (fibreglass)
StandardANSI MC96.1
Technical Specifications
| Construction | |
| Conductor | Thermocouple alloy pair (Type J / K / T / R-S per requirement) |
| Conductor size range | 0.5 – 2.5 sq.mm |
| Number of cores/pairs | 1 pair / 2 pair, shielded or unshielded |
| Insulation | PVC / Glass-fibre / Fibreglass (per temperature grade) |
| Inner sheath | Extruded PVC bedding (multi-pair) |
| Shielding/screen | Overall shield + drain wire (optional) |
| Armour | GI wire braid (optional, for fibreglass variant) |
| Outer sheath | PVC / FRLS or fibreglass braid (high-temp variant) |
| Ratings & Standards | |
| Voltage grade | Signal level (not power-rated) |
| Temperature rating | -20°C to 105°C (PVC); up to 400°C (fibreglass) |
| Applicable standards | ANSI MC96.1, BS EN 60584-3 (colour coding) |
| Special properties | Colour-coded per thermocouple type, matched thermal EMF |
Thermocouple & Extension Cable Colour Codes
ANSI MC96.1 and IEC 584-3 colour coding, alloy combinations and EMF output by thermocouple type.
| ANSI Code | ANSI MC 96.1 Colour Coding | Alloy Combination | Maximum T/C Grade Temp. Range | EMF (mV) Over Max. Temp. Range | IEC 584-3 Colour Coding | IEC Code | ||
|---|---|---|---|---|---|---|---|---|
| Thermocouple | Extension | + Lead | − Lead | |||||
| K | Nickel-ChromiumNi-Cr | Nickel-AluminumNi-Al | -270 to 1372°C-454 to 2501°F | -6.458 to 54.886 | K | |||
| J | IronFe (magnetic) | Constantan Copper-NickelCu-Ni | -210 to 1200°C-346 to 2193°F | -8.095 to 69.553 | J | |||
| T | CopperCu | Constantan Copper-NickelCu-Ni | -270 to 400°C-454 to 752°F | -6.258 to 20.872 | T | |||
| E | Nickel-ChromiumNi-Cr | Constantan Copper-NickelCu-Ni | -270 to 1000°C-454 to 1832°F | -9.835 to 76.373 | E | |||
| N | NicrosilNi-Cr-Si | NisilNi-Si-Mg | -270 to 1300°C-450 to 2372°F | -4.345 to 47.513 | N | |||
| S | None Established | Platinum-10% RhodiumPt-10%Rh | PlatinumPt | -50 to 1768°C-58 to 3214°F | -0.236 to 18.693 | S | ||
| R | None Established | Platinum-13% RhodiumPt-13%Rh | PlatinumPt | -50 to 1768°C-58 to 3214°F | -0.226 to 21.101 | R | ||
| B | None Established | Platinum-30% RhodiumPt-30%Rh | Platinum-6% RhodiumPt-6%Rh | 0 to 1820°C32 to 3308°F | 0 to 13.820 | B | ||
Colour illustrations show the jacket with the positive (+) and negative (−) conductor insulation. Supplied as per the ANSI MC96.1 or IEC 584-3 standard of your choice.
Applications
Thermocouple signal extension
Furnace & kiln temperature monitoring
Process temperature instrumentation
Boiler & heat-treatment plants